Home > Relays > Current Sensing Relays >

Macromatic 24V Plug-in Overcurrent Sensing Relay


Macromatic CAP10AD68
Macromatic CAP10AD68 24V Plug-in Overcurrent Sensing Relay
 
Alternative Views:


Price: $118.47
Note: Ships in 5-10 Business Days
MFG P/N: CAP10AD68
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CAP10AD68
Qty:

Description
 

The Macromatic CAP10AD68 is an overcurrent sensing relay. This 11 pin plug in relay has an input voltage of 24V. It monitors both AC and DC current with an output of 10A SPDT. It has three knobs on top to adjust the current range (threshold), startup time delay, and drop-out setting (hysteresis). Current range is selectable by connecting the corresponding terminal and the COM terminal (see Wiring Diagram). The CAP10AD68 uses an 11 pin 70170-D octal socket. Can be compatible with the Crouzet LIRT and DIRT series. Note: Image is an approximation. Actual part may differ.

DC
5-100 mA
0.05-1 A
0.5-10 A

AC:
3.5-70.7 mA
0.035-0.707 A
0.35-7.07 A

Specifications

  • Relay Function- Overcurrent Sensing
  • Input Voltage- 24V AC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal at 50/60 Hz
  • Load- Less than 5VA
  • Response Times- Pick up & Drop out: Fixed 100 milliseconds, Sensing delay on start-up: 0.1-10 Seconds
  • Output Contacts- 10A @ 240V AC / 7A @ 28V DC SPDT, 1/4 HP @ 120V AC (N.O.)
  • Life Expectancy- Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Operating Temperature- -28 C to 55 C (-18 F to 131 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
  • Approvals- UL and CUL Recognized, C-UL-US Listed (with Socket)

The CAP10AD68 has latching and non-latching modes of operation.

Latching- If a normally closed contact is connected to pins 9 & 11, the relay will be in latching mode. Once the input voltage is introduced, the LED turns green and the start-up sensing time delay is finished the relay starts monitoring. The time delay is adjustable between 0.1-10 seconds. The unit energizes when the current rises above the pick-up setting, which is adjustable. The LED then turns red. When the current drops below the adjustable drop-out setting (5-50% of the pick-up) and the normally closed contact opens, the relay de-energizes. The LED goes back to green. The drop-out setting should be at 5% in latching mode.

Non-Latching- If there is no circuit with pins 9 & 11, the relay is in non-latching mode. Once the input voltage is introduced, the LED turns green and the start-up sensing time delay is finished the relay starts monitoring. The unit energizes when the current rises above the pick-up setting and the LED is red. When the current drops below the drop-out setting, the relay de-energizes and the LED is green again.

Macromatic CAP Series Relay Installation Manual

24V AC Overcurrent Sensing Relay with Plug-in Style Housing


Related Products
Macromatic 11 Pin Octal Socket
Price: $9.45

Add
Macromatic 70170-D 11 Pin Octal Socket



Lumberg Automation RSHS 8Y-922/2 M M12 Power / Data Cordset, Male Receptacle, 8 Pin, 2 M $63.75
Mencom USB Style B to Style A, M25 Port Adapter $46.18