Red Lion Temperature Panel Meter, 5 Digit, Red LED, AC


Red Lion Temperature Panel Meter, 5 Digit, Red LED
Red Lion PAXT0000 Temperature Panel Meter, 5 Digit, Red LED, AC
 
Alternative Views:


Price: $365.00
Note: Call 800-966-2345 for Lead Time
MFG P/N: PAXT0000
MFG: Red Lion
Weight (lbs): 0.65



Availability:
In Stock
Product Code: PAXT0000
Qty:

Description
 

The Red Lion PAXT0000 PAX series temperature panel meter has a 5 digit, red LED display in a 1/8 DIN housing. The signal totalizer is used for calculating a time-input product or counting batch weighing operations. Four setpoint outputs and communications capabilities are available as separate option cards. Communication options include RS232, RS485, Modbus, DeviceNet, and Profibus DP. It is possible to have a computer remotely control the meter outputs. An option card can also create a linear DC output signal. The front panel has 5 function keys, with 3 being programmable. AC powered

Features

  • Thermocouple & RTD Panel Meter
  • 1/8 DIN Housing
  • 5 Digit, Red LED Display
  • Conforms to ITS-90 Standards
  • Fahrenheit or Celsius Unit Overlay w/Backlight
  • Custom Scaling for Non-Standard Probes
  • Time-Temperature Integrator
  • 16 Bit Resolution A/D Converter
  • Field Upgradeable Option Cards
  • 85 to 250 VAC Input Power
  • NEMA 4X/IP65 - Front Panel
  • Red LEDs Readable in Bright Sunlight
  • Adjustable Brightness Fits Surrounding Environment
  • MAX & MIN Reading Memory w/Programmable Capture Time
  • Parameters Can be Completely or Partially Locked After Setup
  • Not made to directly command motors, valves or actuators without safeguards

Red Lion PAX Series Analog Meter User Manual

Specifications

Display
5 digit, 0.56" (14.2 mm) red sunlight readable LEDs, (-19999 to 99999)
Annunciators:
MAX, MIN, TOT, SP1 - setpoint alarm 1 active, SP2 - setpoint alarm 2 active, SP3 - setpoint alarm 3 active state, SP4 - setpoint alarm 4 active
Power Requirements
AC Power: 85 to 250 VAC, 50/60 Hz, 15 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs.
Memory
Nonvolatile E2PROM retains programmable parameters & display values
User Inputs
Three programmable user inputs
Max. Continuous Input: 30 VDC
Isolation To Sensor Input Common: Not isolated
Response Time: 50 msec. max.
Logic State: Jumper selectable for sink/source logic
Update Rates
A/D conversion rate: 20 readings/sec.
Step response: 200 msec. max. to within 99% of final readout value
(digital filter and internal zero correction disabled)
700 msec. max. (digital filter disabled, internal zero correction enabled)
Display update rate: 1 to 20 updates/sec.
Setpoint output on/off delay time: 0 to 3275 sec.
Analog output update rate: 0 to 10 sec
Max./Min. capture delay time: 0 to 3275 sec
Low Frequency Noise Rejection
Normal Mode: > 60 dB @ 50 or 60 Hz +/-1%, digital filter off
Common Mode: >100 dB, DC to 120 Hz
Readout
Resolution: Variable: 0.1, 0.2, 0.5, or 1, 2, or 5 degrees
Scale: F or C
Offset Range: -19,999 to 99,999 display units
Thermocouple Inputs
Input Impedance: 20 MOhm
Lead Resistance Effect: 0.03 µV/ohm
Max. Continuous Overvoltage: 30 V
RTD Inputs
Type: 3 or 4 wire, 2 wire can be compensated for lead wire resistance
Excitation current: 100 ohm range: 165 µA
10 ohm range: 2.6 mA
Lead resistance: 100 ohm range: 10 ohm/lead max.
10 ohm range: 3 ohms/lead max.
Max. continuous overload: 30 V
Custom Range
Up to 16 data point pairs
Input range: -10 to 65 mV
0 to 400 ohms, high range
0 to 25 ohms, low range
Display range: -19999 to 99999
Totalizer
Time Base: second, minute, hour, or day
Batch: Can accumulate (gate) input display from a user input
Time Accuracy: 0.01% typical
Decimal Point: 0 to 0.0000
Scale Factor: 0.001 to 65.000
Low Signal Cut-out: -19,999 to 99,999
Total: 9 digits, display alternates between high order and low order readouts
Custom Linearization
Data Point Pairs: Selectable from 2 to 16
Display Range: -19,999 to 99,999
Decimal Point: 0 to 0.0000
Ice Point Compensation: user value (0.00 to 650.00 µV/°C)
Standards Compliance
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
EN 61010-1: General Requirements
EN 61010-2-030: Particular Requirements for Testing and Measuring Circuits
RoHS Compliant
UL Recognized Component: File #E179259
UL Recognized Component: File #E156876
UL Listed: File #E137808
Type 4X Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
Physical
Operating Temperature: 0 C to 50 C (32 F to 122 F)
Storage Temperature: -40 C to 60 C (-40 F to 140 F)
Humidity: 85% max. relative humidity (non-condensing)
Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.
Shock to IEC 68-2-27: Operational 25 g (10 g relay).
Altitude: Up to 2000 meters
Construction: NEMA 4X/IP65 outdoor use, IP20 Touch Safe, Installation Category II, Pollution Degree 2,
One piece bezel/case; flame resistant; Synthetic rubber keypad; panel gasket & mounting clip
Connection: High Compression Cage-Clamp Terminal Block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
Dimensions: 1.95" x 3.8" x 4.2"