Home > Panel Meters > PAX 1/8 DIN Intelligent Panel Meters >

Red Lion Strain Gage Input Panel Meter, 5 Digit, Green LED, DC


Red Lion Strain Gage Input Panel Meter, 5 Digit, Green LED
Red Lion PAXS0110 Strain Gage Input Panel Meter, 5 Digit, Green LED, DC
 
Alternative Views:


Price: $613.00
Note: Call 800-966-2345 for Lead Time
MFG P/N: PAXS0110
MFG: Red Lion
Weight (lbs): 0.65



Availability:
In Stock
Product Code: PAXS0110
Qty:

Description
 

The Red Lion PAXS0110 PAX series strain gage input panel meter has a 5 digit, green LED display in a 1/8 DIN housing. The signal totalizer is used for calculating a time-input product or counting batch weighing operations. Four setpoint outputs and communications capabilities can be achieved with separate option cards. Communication options include RS232, RS485, Modbus, DeviceNet, and Profibus DP. A computer can also remotely control the meter outputs. Using an option card can create a linear DC output signal. The front panel has 5 function keys, with 3 being programmable. DC powered

Features

  • Strain Gage Input
  • 1/8 DIN Housing
  • 5 Digit, Green LED Display
  • Load Cell, Pressure and Torque Bridge Inputs
  • +/- 24 mV or +/- 240 mV Inputs
  • 5 or 10 VDC Bridge Excitation
  • Programmable Auto Zero Tracking
  • 16 Bit Resolution A/D Converter
  • 11 to 36 VDC (24 VDC nominal) Input Power
  • Field Upgradeable Option Cards
  • NEMA 4X/IP65 - Front Panel
  • Adjustable Brightness Fits Surrounding Environment
  • MAX & MIN Reading Memory w/Programmable Capture Time
  • Parameters Can be Completely or Partially Locked After Setup
  • Not made to directly command motors, valves or actuators without safeguards

Red Lion PAX Series Analog Meter User Manual

Specifications

Display
5 digit, 0.56" (14.2 mm) standard green LEDs, (-19999 to 99999)
Annunciators:
MAX, MIN, TOT, SP1 - setpoint alarm 1 active, SP2 - setpoint alarm 2 active, SP3 - setpoint alarm 3 active state, SP4 - setpoint alarm 4 active
Power Requirements
DC Power: 11 to 36 VDC, 11 W
AC Power: 24 VAC, +/- 10%, 50/60 Hz, 15 VA
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working)
Memory
Nonvolatile E2PROM retains programmable parameters & display values
User Inputs
Three programmable user inputs
Max. Continuous Input: 30 VDC
Isolation To Sensor Input Common: Not isolated
Response Time: 50 msec. max.
Logic State: Jumper selectable for sink/source logic
Update Rates
A/D conversion rate: 20 readings/sec.
Step response: 200 msec. max. to within 99% of final readout value
(digital filter and internal zero correction disabled)
700 msec. max. (digital filter disabled, internal zero correction enabled)
Display update rate: 1 to 20 updates/sec.
Setpoint output on/off delay time: 0 to 3275 sec.
Analog output update rate: 0 to 10 sec
Max./Min. capture delay time: 0 to 3275 sec
Low Frequency Noise Rejection
Normal Mode: > 60 dB @ 50 or 60 Hz +/-1%, digital filter off
Common Mode: >100 dB, DC to 120 Hz
Connection Type
4-wire bridge (differential)
2-wire (single-ended)
Common Mode Range
(w.r.t. input common): 0 to +5 VDC
Rejection: 80 dB (DC to 120 Hz)
Bridge Excitation
Jumper Selectable: 5 VDC @ 65 mA max., +/-2%
10 VDC @ 125 mA max., +/-2%
Temperature coefficient (ratio metric): 20 ppm/°C max.
Totalizer
Time Base: second, minute, hour, or day
Batch: Can accumulate (gate) input display from a user input
Time Accuracy: 0.01% typical
Decimal Point: 0 to 0.0000
Scale Factor: 0.001 to 65.000
Low Signal Cut-out: -19,999 to 99,999
Total: 9 digits, display alternates between high order and low order readouts
Custom Linearization
Data Point Pairs: Selectable from 2 to 16
Display Range: -19,999 to 99,999
Decimal Point: 0 to 0.0000
Standards Compliance
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
EN 61010-1: General Requirements
EN 61010-2-030: Particular Requirements for Testing and Measuring Circuits
RoHS Compliant
UL Recognized Component: File #E179259
UL Listed: File #E137808
Type 4X Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
Physical
Operating Temperature: 0 C to 50 C (32 F to 122 F)
Storage Temperature: -40 C to 60 C (-40 F to 140 F)
Humidity: 85% max. relative humidity (non-condensing)
Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.
Shock to IEC 68-2-27: Operational 25 g (10 g relay).
Altitude: Up to 2000 meters
Construction: NEMA 4X/IP65 outdoor use, IP20 Touch Safe, Installation Category II, Pollution Degree 2,
One piece bezel/case; flame resistant; Synthetic rubber keypad; panel gasket & mounting clip
Connection: High Compression Cage-Clamp Terminal Block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
Dimensions: 1.95" x 3.8" x 4.2"

Panel Meter Comparison Chart