The Red Lion PAXP0000 PAX series process input panel meter has a 5 digit, red LED display in a 1/8 DIN housing. The signal totalizer is used for calculating a time-input product or counting batch weighing operations. Four setpoint outputs and communications capabilities are possible with separate option cards. Communication options include RS232, RS485, Modbus, DeviceNet, and Profibus DP. It is possible to have a computer remotely control the meter outputs. An option card can also create a linear DC output signal. The front panel has 5 function keys, with 3 of them being programmable. AC powered
Features
- Process Input
- 1/8 DIN Housing
- 5 Digit, Red LED Display
- 20 mA or 10 VDC Input
- Field Upgradeable Option Cards
- 24 VDC Transmitter Power
- 16 Bit Resolution A/D Converter
- 85 to 250 VAC Input
- NEMA 4X/IP65 - Front Panel
- Red LEDs Readable in Bright Sunlight
- Adjustable Brightness Fits Surrounding Environment
- MAX & MIN Reading Memory w/Programmable Capture Time
- Parameters Can be Completely or Partially Locked After Setup
- Not made to directly command motors, valves or actuators without safeguards
Red Lion PAX Series Analog Meter User Manual
Specifications
Display 5 digit, 0.56" (14.2 mm) red sunlight readable LEDs, (-19999 to 99999) Annunciators: MAX, MIN, TOT, SP1 - setpoint alarm 1 active, SP2 - setpoint alarm 2 active, SP3 - setpoint alarm 3 active state, SP4 - setpoint alarm 4 active Power Requirements AC Power: 85 to 250 VAC, 50/60 Hz, 15 VA Isolation: 2300 Vrms for 1 min. to all inputs and outputs. Memory Nonvolatile E2PROM retains programmable parameters & display values User Inputs Three programmable user inputs Max. Continuous Input: 30 VDC Isolation To Sensor Input Common: Not isolated Response Time: 50 msec. max. Logic State: Jumper selectable for sink/source logic Update Rates A/D conversion rate: 20 readings/sec. Step response: 200 msec. max. to within 99% of final readout value (digital filter and internal zero correction disabled) 700 msec. max. (digital filter disabled, internal zero correction enabled) Display update rate: 1 to 20 updates/sec. Setpoint output on/off delay time: 0 to 3275 sec. Analog output update rate: 0 to 10 sec Max./Min. capture delay time: 0 to 3275 sec Low Frequency Noise Rejection Normal Mode: > 60 dB @ 50 or 60 Hz +/-1%, digital filter off Common Mode: >100 dB, DC to 120 Hz Excitation Power: Transmitter Power: 24 VDC, +/-5%, regulated, 50 mA max. Totalizer Time Base: second, minute, hour, or day Batch: Can accumulate (gate) input display from a user input Time Accuracy: 0.01% typical Decimal Point: 0 to 0.0000 Scale Factor: 0.001 to 65.000 Low Signal Cut-out: -19,999 to 99,999 Total: 9 digits, display alternates between high order and low order readouts Custom Linearization Data Point Pairs: Selectable from 2 to 16 Display Range: -19,999 to 99,999 Decimal Point: 0 to 0.0000 Standards Compliance CE Approved EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A EN 61010-1: General Requirements EN 61010-2-030: Particular Requirements for Testing and Measuring Circuits RoHS Compliant UL Recognized Component: File #E179259 UL Listed: File #E137808 Type 4X Enclosure rating (Face only) IP65 Enclosure rating (Face only) IP20 Enclosure rating (Rear of unit) Physical Operating Temperature: 0 C to 50 C (32 F to 122 F) Storage Temperature: -40 C to 60 C (-40 F to 140 F) Humidity: 85% max. relative humidity (non-condensing) Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g. Shock to IEC 68-2-27: Operational 25 g (10 g relay). Altitude: Up to 2000 meters Construction: NEMA 4X/IP65 outdoor use, IP20 Touch Safe, Installation Category II, Pollution Degree 2, One piece bezel/case; flame resistant; Synthetic rubber keypad; panel gasket & mounting clip Connection: High Compression Cage-Clamp Terminal Block Wire Strip Length: 0.3" (7.5 mm) Wire Gage: 30-14 AWG copper wire Torque: 4.5 inch-lbs (0.51 N-m) max. Dimensions: 1.95" x 3.8" x 4.24"
|
|
|
|
|
|
|