The Red Lion PAXLIA00 PAX LI Lite series AC current panel meter has a 3 1/2 digit, red LED display in a 1/8 DIN housing. It features selectable AC current ranges, built-in scaling provisions, and selectable decimal points. It uses variables that can be displayed as a current readout, such as readouts from pressure, speed, or flow transducers. The display can show a minus sign if the current is in the negative. AC powered. Accessory shunts are available for higher current ranges.
Features
- Selectable AC Current Ranges:
- 0 to 199.9uA/199.9mV, 0 to 1.999mA, 0 to 19.99mA, 0 to 199.9mA, 0 to 1.999A
- 1/8 DIN Housing
- 3 1/2 Digit, Red LED Display w/Polarity
- Built In Scaling Provisions
- Selectable Decimal Point Location
- Auto Zeroing Circuits
- Over-Range Indication
- NEMA 4X/IP65 - Front Panel
Red Lion PAX LI Lite Series User Manual
Specifications
Display 3 1/2 digit, 0.56" (14.2 mm) red LEDs Power Requirements 115 or 230 VAC, switch selectable. Allowable power line variation +/-10%, 50/60 Hz, 6 VA. Isolation: 2300 Vrms for 1 min. between input and supply Working Voltage: 300 V max., CAT II Accuracy (45-500 Hz)
199.9 µA/199.9 mV, 1.999 mA, 19.99 mA: +/-(0.1% of Reading + 3 digits) 199.9 mA: +/-(0.15% of Reading + 3 digits) 1 A: +/-(0.5% of Reading + 3 digits) Max Voltage on Lowest Input Range: 75 VAC or DC Max Voltage on Terminal Block: 300 VAC or DC Response Time to Step Change Input: 1 sec. nominal Reading Rate: 2.5 readings/sec., nominal Common Mode Voltage (Comm to Earth): 350 volt peak Max Currents 199.9 uA through 19.99 mA: 10 times max. range current 199.9 mA: 1 A 1.999 A: 3 A Standards Compliance UL Recognized Component, File # E179259, UL61010A-1, CSA C22.2 No. 61010-1 UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95 Type 4X Enclosure rating (Face only), UL50 IECEE CB Scheme Test Report # 04ME11209-20041018 IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for measurement, control, and laboratory use, Part 1. IP65 Enclosure rating (Face only), IEC 529 Electromagnetic Compatibility: See user manual Physical Operating Temperature: 0 C to 60 C (32 F to 140 F) Storage Temperature: -40 C to 80 C (-40 F to 176 F) Humidity: 85% max. relative humidity (non-condensing) Vibration to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z direction for 1.5 hours, 2 g's. Shock to IEC 68-2-27: Operational 30 g, 11 msec in 3 directions Altitude: Up to 2000 meters Construction: NEMA 4X/IP65 outdoor use, Installation Category II, Pollution Degree 2, One piece bezel/case; flame resistant; panel gasket & mounting clip Connection: High Compression Cage-Clamp Terminal Block Wire Strip Length: 0.3" (7.5 mm) Wire Gage: 30-14 AWG copper wire Torque: 4.5 inch-lbs (0.51 N-m) max. Dimensions: 1.95" x 3.8" x 4.2"
|
|
|
|
|
|
|