|
|
|
|
The Red Lion PAXI0120 PAX series
dual counter/rate panel meter has a 6 digit, green LED display in a 1/8 DIN housing. The display offers 0.56" numbers. Compatible inputs include switch contacts, CMOS & TTL circuit outputs, magnetic pickups, and RLC sensors. Four setpoint outputs can be provided through an optional digital output plug in card. It has communications capability through separate option cards, including RS232, RS485, Modbus, DeviceNet, and Profibus DP. Another option card creates a linear DC output signal. AC powered
Features
- 1/8 DIN Housing
- 6 Digit, Green LED Display
- User Selectable Input Modes
- Rate Indication
- 5 Keys on Front Panel (3 Are Programmable Function Keys)
- Up to 3 Count Displays or a Serial Slave
- 10 Point Scaling for Non Linear Processes
- Four Setpoint Alarm Outputs (w/ Option card)
- Communications & Bus Capabilities (w/ Option card)
- Retransmitted Analog Output (w/Option card)
- Crimson Programming Software
- Ethernet (w/External Gateway)
- NEMA 4X/IP65 - Front Panel
- Accommodates Directional, Uni-Directional, & Quadrature Signals
- Adjustable Brightness Intensity to Fit Surrounding Environment
- MAX & MIN Reading Memory w/Programmable Capture Time
- Parameters Can be Completely or Partially Locked After Setup
- Should not be used to directly command motors, valves, and actuators without safeguards
Red Lion PAX Series User Manual
Specifications
Display 6 digit, 0.56" (14.2 mm) standard green LED Annunciators: A, B, C, r - Rate, H - Max Rate, L - Min Rate, OF - Upper significant digit display of counter, SP1 - setpoint 1 output state, SP2 - setpoint 2 output state, SP3 - setpoint 3 output state, SP4 - setpoint 4 output state Power Requirements AC Power: 85 to 250 VAC, 50/60 Hz, 18 VA Isolation: 2300 Vrms for 1 min. to all inputs and outputs. (300 V working) Sensor Power 12 VDC, +/-10%, 100 mA max. Short circuit protected Memory Nonvolatile memory retains programmable parameters & display values User Inputs Three programmable user inputs Max. Continuous Input: 30 VDC Isolation To Sensor Input Commons: Not isolated Logic State: Jumper selectable for sink/source logic Response Time: 6 msec. typical; function dependent. Output Response Time: 25 microsec.; add 6 msec (typical) if a relay card is installed Timed Output Accuracy: Counter = +/- 0.01% + 10 msec. Rate = +/- 0.01% + 20 msec Rate Display Accuracy: +/-0.01% Minimum Frequency: 0.01 Hz Maximum Frequency: See User Manual Maximum Display: 5 Digits: 99999 Adjustable Display (low) Update: 0.1 to 99.9 seconds Counter Displays Maximum display: 8 digits: +/- 99999999 (greater than 6 digits, the display alternates between high order and low order.) Prescaler Output NPN Open Collector: ISNK = 100 mA max. @ VOL = 1 VDC max. VOH = 30 VDC max. With duty cycle of 25% min. and 50 % max Standards Compliance CE Approved EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A EN 61010-1: General Requirements EN 61010-2-030: Particular Requirements for Testing and Measuring Circuits RoHS Compliant UL Recognized Component: File #E179259 UL Listed: File #E137808 Type 4X Enclosure rating (Face only) IP65 Enclosure rating (Face only) IP20 Enclosure rating (Rear of unit) Physical Operating Temperature: 0 C to 50 C (32 F to 122 F) Storage Temperature: -40 C to 60 C (-40 F to 140 F) Humidity: 85% max. relative humidity (non-condensing) Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g. Shock to IEC 68-2-27: Operational 25 g (10 g relay). Altitude: Up to 2000 meters Construction: NEMA 4X/IP65 outdoor use, IP20 Touch Safe, Installation Category II, Pollution Degree 2, One piece bezel/case; flame resistant; Synthetic rubber keypad; panel gasket & mounting clip Connection: High Compression Cage-Clamp Terminal Block Wire Strip Length: 0.3" (7.5 mm) Wire Gage: 30-14 AWG copper wire Torque: 4.5 inch-lbs (0.51 N-m) max. Dimensions: 1.95" x 3.8" x 4.2"
|
|
|
|
|
|
|