Home > Panel Meters > C48 1/16 DIN Counters & Timers >

Red Lion Panel Meter, Dual Preset Timer, AC, Dual Relay Outputs


Red Lion C48TD102 Panel Meter, Dual Preset Timer
Red Lion C48TD102 Panel Meter, Dual Preset Timer, AC, Dual Relay Outputs
 
Alternative Views:


Price: $327.00
Note: Please call or email [email protected] for alternatives
MFG P/N: C48TD102
MFG: Red Lion
Weight (lbs): 0.38

Quantity in Stock :(Out of Stock)


Availability:
Out of Stock
Product Code: C48TD102
Qty:

Description
 

The Red Lion C48TD102 C48 series panel meter is a dual preset timer with dual relay outputs. It features a 2 line, 6 digit, transmissive backlit LCD display with 1/16 DIN housing. The backlit display has a red digital readout on the top line and a green readout on the lower line. The resistance to noise interference makes it perfect for industrial use. AC powered. Note: This timer is not made for directly controlling motors, valves, or actuators that do not have safeguards.

Features

  • Two Presets
  • 12 Timing Range Modes
  • Dual Line, 6 Digit Transmissive LCD Display w/Backlighting
  • Red Top Line & Green Lower Line
  • Dual Relay Outputs
  • 85 to 250 VAC Input Power
  • NEMA 4X/IP65 - Front Panel
  • Field Replaceable Relay Output Board
  • Status Indicators for Outputs
  • Programmable User Inputs
  • Function Keys on Front Panel
  • Lightweight Black Plastic Housing Withstands Impact
  • Several Panel Meters Can be Stacked Horizontally or Vertically

Red Lion C48T Series User Manual

Specifications

Display
Main Display: 0.3" digits
Secondary Display: 0.2" digits
Annunciators: Value- PRS, 1, & 2; Output- 01 and 02
Power Requirements
AC Power: 85-250 VAC, 50/60 Hz, 9 VA max
DC Power: 11-14 VDC @ 150 mA max
Memory
Nonvolatile E2PROM retains all programmable parameters and timer values
Sensor Power
+12 VDC (+/- 15%) @100 mA max
Count Inputs A & B
Current Sourcing: 3.9KOhm pull-down, VIN max = 30 VDC
Current Sinking: 7.8KOhm pull-up to 12 VDC; ISNK = 1.8 mA max
Debounce: 50 Hz max
Lo Bias: VIL = 1.5 VDC max., VIH = 3.75 VDC min.
Hi Bias: VIL = 5.5 VDC max., VIH = 7.5 VDC min
User Inputs
Current Sinking: VIL = 1.5 VDC max, 22 KOhm pull-up to 5 VDC
Current Sourcing: VIH = 3.5 VDC min., VIN max = 30 VDC; 22 KOhm pulldown
Run/Stop Response Time: 250 usec max.
User Input Response Time: 5 msec max.
Time Accuracy: +/- 0.01%
Outputs
Relay: Form A contact, Rating = 5 A @ 250 VAC, 30 VDC (resistive load), 1/10 HP @ 120 VAC (inductive load)
Relay Life Expectancy: 100,000 cycles min. at max. load rating
Standards Compliance
UL & CUL Recognized
Electrostatic Discharge: EN 61000-4-2
Electromagnetic RF Fields: EN 61000-4-3
Fast Transients (burst): EN 61000-4-4
RF Conducted Interference: EN 61000-4-6
Simulation of Cordless Phone: ENV 50204
RF Interference: EN 55011
Physical
Operating Temperature: 0 C to 50 C (32 F to 122 F)
Storage Temperature: -40 C to 70 C (-40 F to 158 F)
Humidity: 85% max. relative humidity (non-condensing) from 0 C to 50 C.
Altitude: Up to 2000 meters
Housing: Black Plastic
Electrical Connection: Wire clamping screw terminals
Dimensions: 1.95" x 1.95" x 4.54"

This timer features 42 operating modes & 12 timing ranges, measuring from thousandths of a second up to minutes and hours. Timing can be set to consistently accumulate or reset for each power cycle. Timing units (seconds, minutes, hours) are kept separate on the display by decimal points. It accommodates On Delay, Off Delay, Single Shot, & Repetitive Auto Cycling timing modes. Inputs include a Run/Stop Input, and three programmable User Inputs. The function keys on the front control programming modes & data values, changing the display, and resetting. Data entry is done through digit entry or automatic scrolling. Run/Stop and User inputs can be sinking (active low) or sourcing (active high) through a single plug jumper. The relay output boards are all field replaceable.

Panel Meter Comparison Chart