The Red Lion PMM000I0AN000000 is an analog output module. It is used specifically with the PM-50 series of Red Lion graphical panel meters. It is 0 or 4 to 20 mA or 0 to 10 VDC, and is removable if necessary. PM-50 series panel meters accept additional optional modules for serial communications, Ethernet, analog output, AC to DC power, and setpoint output. The 4.3 inch version accepts up to 5 modules while the 3.5 inch version accepts up to 3. Only one module of each type (communications, power, output) can be added.
Specifications
Power
- Power comes from the panel meter - Must use a Class 2 circuit according to National Electrical Code (NEC), NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited Power Supply (LPS) according to IEC/EN 60950-1 or Limited-energy circuit according to IEC/EN 61010-1.
- Max Power: 1.3 Watts
Analog Output
- Types: 0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA
- Isolation To Sensor & User Input Commons: 500 Vrms
- Accuracy: 0 to 10 V or ±10 V range: 0.1% of full scale (-10 to 55 °C), 0 to 20 mA or 4 to 20 mA: 0.1% of full scale (18 to 28 °C), 0.25% of full scale (-10 to 55 °C)
- Compliance for current output: 500 ohm max. (10 V max.)
- Minimum load for voltage output: 500 ohm min. (20 mA max.)
- Effective Resolution: Full 16-bit (Signed)
- Compliance: 20 mA: 500 Ω load max. (self-powered)
Connections
- High compression cage-clamp terminal blocks
- Wire Strip Length: 0.32-0.35" (8-9 mm)
- Wire Gauge Capacity: Four 28 AWG (0.32 mm) solid, two 20 AWG (0.61 mm) or one 16 AWG (2.55 mm)
Environmental
- Operating Temperature: 14 F to 131 F
- Storage Temperature: -40 F to 185 F
- Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g
- Shock to IEC 68-2-7: Operational 20 g
- Humidity: 85% max Relative Humidity non-condensing
- Altitude: Up to 2000 meters
- Installation Category II, Pollution Degree 2 as defined in IEC/EN 60664-1
- Housing: Plastic
Approvals
- CE Approval
- EN 61326-1 Immunity to Industrial Locations
- Emission CISPR 11 Class A
- IEC/EN 61010-1
- RoHS Compliant
- UL Hazardous: File # E317425
- IP 25 Enclosure
Red Lion Analog Output Module User Manual
|
|
|
|
|
|
|