The Macromatic VMP240AX is a voltage monitor relay. This 8 Pin plug-in relay has a nominal voltage of 240V AC. It checks for over or under voltage errors and has an output of 5A DPDT. The VMP240AX operates with a fixed pick-up & drop-out time delay, adjustable pick-up voltage, and a fixed drop-out voltage. The LED indicator on the VMP240A is red to show when the relay is energized or green when it is not. Pilot duty rating. It uses an 8 Pin 70169-D octal socket and features true RMS voltage measurement for more precise sensing. Note: 10A version pictured

Specifications

  • Relay Function- Over/Undervoltage
  • Nominal Voltage- 240V AC
  • Output- 5A DPDT
  • Pick-up Voltage Range- 180-300V AC
  • Drop-out Voltage Range- 135-285V AC (set at 95% of Pick-Up)
  • Setting Accuracy- Max Setting (Adjustable): +5%, -0%
    Min Setting (Adjustable): +0%, -50%
    Fixed Voltage Setting: +/- 2%
  • Repeatability- <1%
  • Load- 30VA
  • Sensing Accuracy- Constant conditions within specifications: +/-2%
    Variable conditions within specifications: +/- 5%
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Voltage Tolerance- +/-50% of Nominal Voltage
  • Output Contacts- 5A @ 277V AC, 5A @ 30V DC, 1/3HP @ 120/240V AC, B300 Pilot Duty
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Response Time- Restart: 1 second, Pick-up: 0.5 seconds, Drop-out: 0.5 seconds
  • Reset- Automatic
  • Transient Protection- 2000V for IEC 61000-4-5 Level 3 (+/-2kV)
  • Dimensions- 2.4" Height x 1.7" Width x 3" Depth
  • Approvals- UL and CUL recognized, CE, UL & CUL listed (with Socket)

When the voltage stays above the preset pick-up voltage (180-300V AC) for a longer period than the pick-up time delay, then the unit is energized. If the voltage goes below the drop-out voltage (135-285V AC) for a longer duration than the drop-out time delay, then it de-energizes. The drop-out time delay is fixed at 0.5 seconds. Whether the VMP240AX monitors for undervoltage or overvoltage situations depends on the type of output contacts being used.

Overvoltage
Overvoltage protection utilizes a normally closed contact. The voltage has to stay below the max setting for the load to be energized while the relay itself remains de-energized. If the voltage goes above this level, the load de-energizes and the relay energizes until voltage goes back down.

Undervoltage
Undervoltage monitoring requires a normally open contact. The load stays on and the relay is energized so long as the voltage stays above the minimum setting. Voltage going below the minimum de-energizes both the load and the relay.

Macromatic VMP Series Relay Installation Instructions

240V AC 5A Voltage Monitor Relay VMP240AX

Additional Product Information

Related Products
Macromatic 8 Pin Octal Socket Macromatic Hold Down Spring
Price: $5.69

Add
Price: $5.09

Add
Macromatic 70169-D 8 Pin Octal Socket Macromatic Hold Down Spring



Cnlinko Snap Fastener RJ45 Male Plug $7.58