The Macromatic TR-6192U is a power triggered Off Delay Time Delay Relay. This programmable multi-range plug-in relay has a universal input voltage of 24-240V AC & 12-125V DC at 50/60Hz, with 10A DPDT output contacts. It has 16 built in time ranges, from 0.05 sec to 100 hours, using a rotary switch. Settings within the time range are made using the potentiometer switch. The TR-6192U uses an 11 pin 70170-D octal socket. This relay replaces TR-61921, TR-61922, TR-61926, & TR-61928.
Note: Image is an approximation. Actual part may differ.
Timing Ranges
- A: 0.05 - 0.5 Sec
- B: 0.1 - 1 Sec
- C: 0.5 - 5 Sec
- D: 1 - 10 Sec
- E: 3 - 30 Sec
- F: 6 - 60 Sec
- G: 0.2 - 2 Min
- H: 0.5 - 5 Min
- I: 1 - 10 Min
- J: 3 - 30 Min
- K: 6 - 60 Min
- L: 0.2 - 2 Hr
- M: 0.5 - 5 Hr
- N: 1 - 10 Hr
- O: 2.4 - 24 Hr
- P: 10 - 100 Hr
Specifications
- Function- Off Delay (Power Trigger)
- Timing Range- 0.05 Sec - 100 Hours
- Input Voltage- 24-240V AC & 12-125V DC
- Output- 10A DPDT
- Voltage Tolerance- AC Operation: 20.4-264V at 50/60 Hz.
DC Operation: 10.2-137.5V
- Load- 3VA max.
- Setting Accuracy- Maximum Setting: +5%, -0%
Minimum Setting: +0%, -50%
- Repeat Accuracy- Greater amount of +/- 0.1% or +/- 50ms
- Reset Time- 0.1 Seconds
- Start Up Time- 0.05 Sec
- Maintain Function Time- 0.01 Sec
- Operating Temperature- -28 C to 65 C (-18 F to 150 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- DPDT 10A @ 240V AC/30V DC,
1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.) B300 & R300 (N.O.); AC15 & DC13
- Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
- Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
- Approvals- UL & CUL recognized, CE, UL & CUL listed (with Socket)
The Off Delay function means that the output is energized through the use of a trigger, in this case, voltage is used. The time delay starts when the trigger is taken out. The output becomes de-energized once the time delay stops. Re-introducing the trigger before the time delay stops resets the time delay. Input voltage must be in place before the trigger and time delay can take effect.
Macromatic TR-6 Series Relay Installation Instructions
Macromatic Time Delay Relay TR-6192U
|
|
|