The Macromatic TR-60621 is a True Off Delay Time Delay Relay. This programmable multi-range plug-in relay has an input voltage of 240V AC and 10A DPDT output contacts. It has 8 built in time ranges, from 0.05 sec to 30 min, using a rotary switch. The TR-60621 uses an 8 pin 70169-D octal socket.
Please Note: Even though this relay is intended to arrive in the OFF state, a shock during transit can trigger the ON state. It is therefore suggested to apply input voltage to the relay for at least 0.1 seconds and then taking it out to make sure the relay is now in the OFF state.
Image is an approximation. Actual part may differ.
Timing Ranges
- A: 0.05 - 5 Sec
- B: 0.1 - 10 Sec
- C: 0.3 - 30 Sec
- D: 0.6 - 60 Sec
- E: 1.8 - 180 Sec
- F: 3 - 300 Sec
- G: 0.1 - 10 Min
- H: 0.3 - 30 Min
Specifications
- Function- True Off Delay
- Timing Range- 0.05 Sec - 30 Min
- Input Voltage- 240V AC
- Output- 10A DPDT
- Voltage Tolerance- AC Operation: +10/-15% of nominal at 50/60 Hz.
DC Operation: +10/-15% of nominal.
- Load- 2VA
- Setting Accuracy- Maximum Setting: +5%, -0%
Minimum Setting: +0%, -50%
- Repeat Accuracy- +/- 50 milliseconds
- Reset Time- 0.1 Seconds
- Start Up Time- 0.05 Sec
- Maintain Function Time- 0.01 Sec
- Temperature- -28 C to 65 C (-18 F to 150 F)
- Output Contacts- DPDT 10A @ 240V AC, 8A @ 28V DC,
1/2HP @ 240V AC, 1/4HP @ 120V AC B300 & R300
- Life- Mechanical: 2,000,000 Operations
Full Load: 100,000 Operations
- Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
- Approvals- UL & CUL Listed (with socket), CE, C UR US
The True Off Delay function energizes the output when the input voltage is started (input voltage needs to be in place for at least 0.5 seconds). The time delay starts when the input voltage is taken out and the output stays energized for the duration, after which it is de-energized. The time delay is reset if the input voltage is reapplied during this process.
Macromatic TR-6 Series Relay Installation Instructions
240V True Off Time Delay Relay TR-60621
|
|
|