The Macromatic TD-83122-40 is a Repeat Cycle OFF Time Delay Relay. This programmable plug-in relay has an input voltage of 120V AC/DC at 50/60Hz and 10A DPDT output contacts. The OFF and ON timing ranges are digitally selected by two sets of 10 position binary DIP switches, from 0.1 to 102.3 seconds. The TD8312240 uses an 8 pin 70169-D octal socket. It features an LED indicator to show the current status of the relay. It shows green when the power is on, and red once the relay is energized.
Note: Image is for reference, actual part may differ
Specifications
- Function- Repeat Cycle OFF
- Timing Range- 0.1 - 102.3 Seconds
- Input Voltage- 120V AC/DC
- Output- 10A DPDT
- Voltage Tolerance- AC Operation: +10/-15% of nominal at 50/60 Hz.
DC Operation: +10/-15% of nominal.
- Load- 2VA
- Setting Accuracy- Constant Voltage/Temp: The greater amount of +/- 0.1% of set time or +/-50ms, Variable Voltage/Temp: The greater amount of +/- 1% of set time or +/- 50ms.
- Repeat Accuracy- Constant Voltage/Temp: The greater amount of +/-0.1% of set time or +/-0.02 sec, Variable Voltage/Temp: The greater amount of +/- 1% of set time or +/- 0.02 sec.
- Reset Time- 0.1 Seconds
- Start Up Time- 0.05 Sec
- Maintain Function Time- 0.01 Sec
- Insulation Voltage- 2000 V
- Operating Temperature- -28 C to 65 C (-18 F to 150 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- DPDT 10A @ 240V AC/30V DC,
1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120V AC (N.C.) B300 & R300, AC15 & DC13
- Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
- Dimensions- 2.4" Height x 1.7" Width x 3" Depth
- Approvals- UL recognized, CE, CSA, UL listed (with Socket)
The Repeat Cycle OFF function means that once the input voltage is introduced, the OFF time delay starts. The relay energizes after this time delay, and stays energized during the ON time delay. After the ON time delay the relay de-energizes and the cycle repeats itself until the input voltage is taken out. There are two sets of DIP switches, one for the OFF delay, and one for the ON delay. Each DIP switch is labeled with a time increment. Move the necessary switches to the ON position and add up their labeled values to set the time delay for both the OFF and ON cycles. For example, to set the time delay for 2.5 seconds, the switches for 0.1, 0.8, & 1.6 would be moved to the ON position.
Macromatic TD-8 Series Relay Installation Instructions
120V AC/DC 0.1-102.3 Second Repeat Cycle OFF Plug-In Timer Relay TD-83122-40
|
|
|