|
The Macromatic TD-80522-40 is an Interval On Time Delay Relay. This programmable plug-in relay has an input voltage of 120V AC/DC at 50/60Hz and 10A DPDT output contacts. The timing ranges are digitally selected by 10 position binary DIP switch, from 0.1 to 102.3 seconds. The TD8052240 uses an 8 pin 70169-D octal socket. It features an LED indicator to show the current status of the relay. It shows green when the power is on, and red once the relay is energized.
Note: Image is for reference, actual part may differ
Specifications
- Function- Interval On
- Timing Range- 0.1 - 102.3 Seconds
- Input Voltage- 120V AC/DC
- Output- 10A DPDT
- Voltage Tolerance- AC Operation: +10/-15% of nominal at 50/60 Hz.
DC Operation: +10/-15% of nominal.
- Load- 2VA
- Setting Accuracy- Constant Voltage/Temp: The greater amount of +/- 0.1% of set time or +/-50ms, Variable Voltage/Temp: The greater amount of +/- 1% of set time or +/- 50ms.
- Repeat Accuracy- Constant Voltage/Temp: The greater amount of +/-0.1% of set time or +/-0.02 sec, Variable Voltage/Temp: The greater amount of +/- 1% of set time or +/- 0.02 sec.
- Reset Time- 0.1 Seconds
- Start Up Time- 0.05 Sec
- Maintain Function Time- 0.01 Sec
- Insulation Voltage- 2000 V
- Operating Temperature- -28 C to 65 C (-18 F to 150 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- DPDT 10A @ 240V AC/30V DC,
1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120V AC (N.C.) B300 & R300, AC15 & DC13
- Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
- Dimensions- 2.4" Height x 1.7" Width x 3" Depth
- Approvals- UL recognized, CE, CSA, UL listed (with Socket)
The Interval On function means that the time delay starts along with the input voltage, energizing the relay. When the time delay stops it is de-energized. In order for the time delay to be reset, the input voltage needs to be taken out. Each DIP switch is labeled with a time increment. Move the necessary switches to the ON position and add up their labeled values to set the time delay. For example, to set the time delay for 2.5 seconds, the switches for 0.1, 0.8, & 1.6 would be moved to the ON position.
Macromatic TD-8 Series Relay Installation Instructions
8 Pin 120V AC/DC 0.1-102.3 Second Time Delay Industrial Relay TD-80522-40
|
|
|