The Macromatic LCP2A100F20 is a single probe pump up (fill) liquid level control relay. This 8 Pin plug-in relay has an input voltage of 120V AC. It monitors the level of conductive liquid (such as tap water, chemical solution, seawater, etc.) in a tank. Sensitivity is adjustable within the set range. Used to monitor liquid levels in the tank for pumps, solenoids, or valves. Electroplating is prevented due to the DC voltage pulsed through the probe, while the fixed time delay prevents rapid cycling. Pilot duty rating.
Note: LCP2B250F2 pictured for reference.
Specifications
- Relay Function- Single Probe Pump Up Liquid Level Control Relay
- Input Voltage- 120V AC
- Output- 10A SPDT
- Sensitivity Range- 4.7K to 100K Ohms
- Voltage Tolerance- AC Operation: +10 / -15% of nominal at 50/60 Hz
- Load- 2 VA
- Probe Voltage- 5V DC Pulsed
- Operating Temperature- -28 C to 65 C (-18 F to 149 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- 10A @ 240V AC / 7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
- Life- Mechanical: 10,000,000 operations, Full Load: 100,000 operations
- Response Time- Pick Up: 20 Seconds, Drop Out: 500 Milliseconds
- Dimensions- 2.4" Height x 1.7" Width x 3.2" Depth
- Approvals- UL and CUL recognized, UL & CUL listed (with Socket)
When the level of conductive liquid goes below the probe, the fixed time delay starts and the LED flashes red. The relay energizes after the time delay and the LED is solid red. It stays this way until the liquid comes back up to the probe. The relay is then no longer energized and the LED is green.