The Macromatic COH05A8BH is a current sensing relay. This encapsulated relay has an input voltage of 24V AC/DC. It checks for overcurrent faults and has an output of 10A SPDT. It monitors AC current, with an adjustable range of 0.5-5A and a trip time delay of 0.5-50 seconds. There is a 5 second sensing time delay on startup. The built-in current transformer provides easy access and greater sensitivity. The encapsulated housing is perfect for use under harsh conditions.
Note: Image is an approximation. Actual part may differ.
Specifications
- Relay Function- Overcurrent
- Current Monitor Range- 0.5-5A
- Time Trip Delay- 0.5-50 seconds
- Sensing Time Delay on Startup- 5 seconds
- Input Voltage- 24V AC/DC
- Output- 10A SPDT
- Input Voltage Tolerance- +10/-15% of nominal
- Load- 2VA
- Current Sensing- Type: Toroidal, through hole wiring
Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
Maximum Allowable Current: Steady-25A Turns; 150A Inrush for 10 Seconds
Trip Point Hysteresis: -5%
- Response Time- Time Delay on Reset (Relay OFF): 100ms
Reset Time: 400ms
- Operating Temperature- -28 C to 65 C (-18 F to 149 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
- Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
- Mounting- Surface mount with 2 #6 screws
- Termination- 0.25" male quick-connect terminals
- Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
- Approvals- UL & CUL Recognized
When the input voltage is introduced and the startup time delay has passed, the relay then starts monitoring for faults. In the event of an overcurrent fault, the AC current rises above the set Fault Trip Current for a longer period than the adjusted time delay. The relay energizes after the time delay and de-energizes once the current goes back below the reset level. The COH05A8BH has an LED indicator which glows red to show if an overcurrent is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.