The Macromatic CAH20A1BF is a current sensing relay. This encapsulated relay has an input voltage of 240V AC. It is made to check for over or undercurrent faults and has an output of 10A SPDT. It monitors AC current, with an adjustable range of 2-20A and a trip time delay of 0.5-50 seconds. There is a 3 second sensing time delay on startup. The built-in current transformer provides greater access and sensitivity, as the wire can be looped around more than once. The encapsulated housing is intended for harsh environments.
Note: Image is an approximation. Actual part may differ.
Specifications
- Relay Function- Over/undercurrent
- Current Monitor Range- 2-20A
- Time Trip Delay- 0.5-50 seconds
- Sensing Time Delay on Startup- 3 Second
- Input Voltage- 240V AC
- Output- 10A SPDT
- Input Voltage Tolerance- +10/-15% of nominal
- Load- 2VA
- Current Sensing- Type: Toroidal, through hole wiring
Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
Trip Point Hysteresis: -5% Overcurrent sensing +5% Undercurrent sensing
- Response Time- Time Delay on Reset (Relay OFF): 100ms
Reset Time: 400ms
- Operating Temperature- -28 C to 65 C (-18 F to 149 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
- Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
- Mounting- Surface mount with two #6 screws
- Termination- 0.25" male quick-connect terminals
- Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
- Approvals- UL & CUL Recognized
With the selector switch, the user chooses whether the relay checks for over or under current errors. The relay starts monitoring for faults once the input voltage is introduced and the startup time delay has passed. If an overcurrent error occurs, the AC current goes above the set Fault Trip Current for longer than the adjusted time delay. The relay energizes after the time delay and stays energized until the current goes below the reset level. In the event of an undercurrent fault, the current needs to go below the set Fault Trip Current for longer than the time delay. Again, the relay energizes after the time delay and will de-energize once the current goes over the reset level. The CAH20A1BF has an LED which glows red to indicate when a fault is detected. Has pilot duty rating. Common applications include process control, monitoring for locked rotor or load loss, or open heater or lamp.
Macromatic CAH Series Relay Installation Manual
CAH20A1BF Macromatic Current Sensing Relay with 3 Second Startup Delay
|
|
|
|
|
|
|