The Macromatic CAH05A2AG is a current sensing relay. This encapsulated relay has an input voltage of 120V. It checks for either over or undercurrent errors and has an output of 10A SPDT. It works with AC current, featuring an adjustable range of 0.5-5A and a trip time delay of 0.15-7 seconds. There is a 4 second sensing time delay on startup. The built-in current transformer promotes easier access and greater sensitivity, since the wire can be looped more than once. The encapsulated housing is intended for use in harsher locations.
Note: Image is an approximation. Actual part may differ.
Specifications
- Relay Function- Over/undercurrent
- Current Monitor Range- 0.5-5A
- Time Trip Delay- 0.15-7 seconds
- Sensing Time Delay on Startup- 4 Second
- Input Voltage- 120V AC
- Output- 10A SPDT
- Input Voltage Tolerance- +10/-15% of nominal
- Load- 2VA
- Current Sensing- Type: Toroidal, through hole wiring
Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
Maximum Allowable Current: Steady-25A Turns; 150A Inrush for 10 Seconds
Trip Point Hysteresis: -5% Overcurrent sensing +5% Undercurrent sensing
- Response Time- Time Delay on Reset (Relay OFF): 100ms
Reset Time: 400ms
- Operating Temperature- -28 C to 65 C (-18 F to 149 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
- Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
- Mounting- Surface mount with two #6 screws
- Termination- 0.25" male quick-connect terminals
- Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
- Approvals- UL & CUL Recognized
A switch allows the user to select whether the relay monitors for over or under current conditions. The relay starts checking for possible faults once the input voltage is introduced. For an overcurrent fault, this occurs when the AC current goes above the set Fault Trip Current for longer than the adjusted time delay. The relay energizes after the time delay and stays energized until the current goes below the reset level. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. Again, the relay energizes after the time delay and will de-energize once the current goes over the reset level. The CAH05A2AG features an LED which glows red to indicate when a fault is detected. Has pilot duty rating. It is perfect for applications such as process control, monitoring for locked rotor or load loss, or open heater or lamp.
Macromatic CAH Series Relay Installation Manual
120V AC Current Sensing Relay Macromatic CAH05A2AG
|
|
|
|
|
|
|