The Macromatic CAH05A2AE is a current sensing relay. This encapsulated relay has an input voltage of 120V. It checks for either over or undercurrent situations and has an output of 10A SPDT. It monitors AC current, with an adjustable range of 0.5-5A and a trip time delay of 0.15-7 seconds. There is a 2 second sensing time delay on startup. The integrated current transformer provides easy access and greater sensitivity, since the wire can be looped more than once. The encapsulated housing is ideal for use under more extreme conditions.
Note: Image is an approximation. Actual part may differ.
Specifications
- Relay Function- Over/undercurrent
- Current Monitor Range- 0.5-5A
- Time Trip Delay- 0.15-7 seconds
- Sensing Time Delay on Startup- 2 Second
- Input Voltage- 120V AC
- Output- 10A SPDT
- Input Voltage Tolerance- +10/-15% of nominal
- Load- 2VA
- Current Sensing- Type: Toroidal, through hole wiring
Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
Maximum Allowable Current: Steady-25A Turns; 150A Inrush for 10 Seconds
Trip Point Hysteresis: -5% Overcurrent sensing +5% Undercurrent sensing
- Response Time- Time Delay on Reset (Relay OFF): 100ms
Reset Time: 400ms
- Operating Temperature- -28 C to 65 C (-18 F to 149 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
- Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
- Mounting- Surface mount with two #6 screws
- Termination- 0.25" male quick-connect terminals
- Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
- Approvals- UL & CUL Recognized
It is possible to choose whether the relay monitors for over or under current conditions through the use of a selector switch. The relay starts checking for possible faults once the input voltage is introduced. For an overcurrent situation, this occurs when the AC current goes above the set Fault Trip Current for longer than the adjusted time delay. The relay energizes after the time delay and stays energized until the current goes below the reset level. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. Again, the relay energizes after the time delay and will de-energize once the current goes over the reset level. The CAH05A2AE features an LED indicator which glows red to show when a fault is detected. Has pilot duty rating. It is perfect for applications such as process control, monitoring for locked rotor or load loss, or open heater or lamp.
Macromatic CAH Series Relay Installation Manual
Macromatic CAH05A2AE Encapsulated Current Sensing Relay
|
|
|
|
|
|
|