Home > Panel Meters > Panel Meter Output Cards and Labeling Kits >

Red Lion Ethernet Communications Module


Red Lion Ethernet Communications Module
Red Lion PMM000CMENT00000 Ethernet Communications Module
 
Alternative Views:


Price: $104.00
Note: Call 800-966-2345 for Lead Time
MFG P/N: PMM000CMENT00000
MFG: Red Lion
Weight (lbs): 0.08



Availability:
In Stock
Product Code: PMM000CMENT00000
Qty:

Description
 

The Red Lion PMM000CMENT00000 is an Ethernet communications module. It is used specifically with the PM-50 series of Red Lion graphical panel meters. It has 10/100 Ethernet, Auto MDI / MDI-X, an RJ-45 jack, and is removable if necessary. PM-50 series panel meters accept additional optional modules for serial communications, Ethernet, analog output, AC to DC power, and setpoint output. The 4.3 inch version accepts up to 5 modules while the 3.5 inch version accepts up to 3. Only one module of each type (communications, power, output) can be added.

Specifications

Power
  • Power comes from the panel meter - Must use a Class 2 circuit according to National Electrical Code (NEC), NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited Power Supply (LPS) according to IEC/EN 60950-1 or Limited-energy circuit according to IEC/EN 61010-1.
  • Max Power: 0.75 Watts
Communications
  • Ethernet Port: 10BaseT/100BaseTX RJ-45 port, auto MDI/MDI-X
  • RJ45 jack is wired as a NIC (Network Interface Card)
  • Isolation from Ethernet network to PM-50: 1500 Vrms
Environmental
  • Operating Temperature: 14 F to 131 F
  • Storage Temperature: -40 F to 185 F
  • Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g
  • Shock to IEC 68-2-7: Operational 20 g
  • Humidity: 85% max Relative Humidity non-condensing
  • Altitude: Up to 2000 meters
  • Installation Category II, Pollution Degree 2 as defined in IEC/EN 60664-1
  • Housing: Plastic
Approvals
  • CE Approval
  • EN 61326-1 Immunity to Industrial Locations
  • Emission CISPR 11 Class A
  • IEC/EN 61010-1
  • RoHS Compliant
  • UL Hazardous: File # E317425
  • IP 25 Enclosure