Macromatic 190-500V Phase Loss/Reversal Monitor Relay


Macromatic PLPU
Macromatic PLPU 190-500V Phase Loss/Reversal Monitor Relay
 
Alternative Views:


Price: $77.90
Note: Ships in 5-10 business days
MFG P/N: PLPU
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: PLPU
Qty:

Description
 

The Macromatic PLPU is a three phase monitor relay that checks for phase reversal and phase loss. This 8 pin plug in relay has a universal voltage range of 190-500V, with an output of 10A SPDT. The LED on top will be green if everything is functioning correctly, or if it is in the process of a restart. The LED will glow or blink red if the relay finds an error. The diagram on top of the unit shows how the LED will indicate the current status. The PLPU uses an 8 pin 70169-D octal socket. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Three Phase (Phase Loss/Reversal)
  • Line-Line Voltage- 190-500V AC
  • Minimum Voltage- 156V
  • Maximum Voltage- 550V
  • Power Consumption- < 40VA
  • Output- 10A SPDT
  • Phase Reversal- Trips if rotation is something other than A-B-C
  • Phase Loss- Trips if Phase A, B or C is lost
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10A @ 277V AC / 7A @ 30V DC; 1 HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Response Time- Restart: 1 sec
    Phase Loss/Reversal: 100ms
  • Dimensions- 2.4" Height x 1.7" Width x 3" Depth
  • Approvals- UL and CUL Recognized, CE, C-UL-US Listed (with Socket)

This unit protects your equipment from phase reversal or phase loss through the use of "True RMS voltage measurement". Analog to digital sensing circuitry in True RMS voltage measurement allows the relay to provide greater precision in monitoring phases and voltages. If a phase is lost, the unit can still monitor all the voltages while indicating the fault, adding to the overall protection. If the system voltage is above 300V, this relay should be used with a 600V rated socket. This electrical relay is energized once the correct voltage is introduced, and the phases are in the correct order. If it detects a phase loss or reversal, the unit will de-energize after a time delay. Once the error is fixed, the relay will energize again without needing any manual reset.

Macromatic PLP Series Relay Installation Manual

Macromatic Three Phase Monitor Relay Comparison Chart

Macromatic PLPU Universal Voltage Phase Monitor Relay

Additional Product Information

Related Products
Macromatic Hold Down Spring Macromatic 8 Pin Octal Socket
Price: $5.09

Add
Price: $5.69

Add
Macromatic Hold Down Spring Macromatic 70169-D 8 Pin Octal Socket