The Macromatic ARP024A3 is an alternating relay. This 8 Pin plug-in relay has a control voltage of 24V with a 10A DPDT cross wired output. This relay is used for applications in which the run time of two loads has to be equalized and when more load capacity is necessary. It uses an 8 pin 70169-D octal socket. This relay is used with a control switch, which starts the alternating action. The output contacts on the relay change state when the initiating switch opens, so the loads alternate. The ARP024A3 has 2 LED indicators that show which load energizes first.
Note: Image is an approximation, actual part may differ
Specifications
- Relay Function- Alternating Relay, DPDT Cross Wired
- Control Voltage- 24V AC/DC
- Output- 10A DPDT Cross Wired
- Voltage Tolerance- +10/-15% of control voltage
- Load- <3VA
- Operating Temperature- -28 C to 65 C (-18 F to 149 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- 10A @ 240V AC / 30V DC, 1/2 HP @ 120/240V AC (N.O.), 1/3 HP @ 120/240V AC (N.C.), B300, R300 (N.O.) Pilot Duty
- Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
- Dimensions- 2.4" Height x 1.7" Width x 3.1" Depth
- Approvals- C UR US, CE, CSA, C UL US Listed (with Socket)
Macromatic ARP Series Relay Installation Manual
ARP024A3 Macromatic 24V Plug In Alternating Relay
|
|
|