Home > Relays > Voltage Monitor Relays >

Macromatic 48V DC Over/Undervoltage Monitor Relay


Macromatic VAKP048D Over/Undervoltage Monitor Relay
Macromatic VAKP048D 48V DC Over/Undervoltage Monitor Relay
 
Alternative Views:


Price: $118.17
Note: Ships in 5-10 Business Days
MFG P/N: VAKP048D
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: VAKP048D
Qty:

Description
 

The Macromatic VAKP048D is a voltage monitor relay. This 8 Pin plug-in relay has a nominal voltage of 48V DC. It monitors against over or under voltage errors and has an output of 10A DPDT. The VAKP048D features an adjustable pick-up voltage & drop-out voltage, with an adjustable drop-out time delay ranging from 0.1-10 sec. It features an LED that is red when the unit is energized or green when it is not. It uses an 8 Pin 70169-D octal socket. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Over/Undervoltage
  • Nominal Voltage- 48V DC
  • Output- 10A DPDT
  • Drop-out Time Delay- 0.1-10 sec
  • Pick-up Voltage Range- 36-60V DC
  • Drop-out Voltage Range- 27-57 DC (75-95% of Pick-Up)
  • Load- <2VA
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Voltage Tolerance- +/-50% of Nominal Voltage
  • Output Contacts- 10A @ 240V AC, 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Response Time- Pick-up: 0.5 sec, Drop-out: 0.1-10 sec
  • Reset- Automatic
  • Transient Protection- 2000V for IEC 61000-4-5 Level 3 (+/-2kV)
  • Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
  • Approvals- UL and CUL recognized, CE, UL & CUL listed (with Socket)

When the voltage stays above the preset pick-up voltage (36-60V DC), then the unit is energized. If the voltage goes below the preset drop-out for greater duration than the drop-out time delay, then it de-energizes. Whether the VAKP048D operates for undervoltage or overvoltage protection is subject to the kind of output contacts being used.

Overvoltage
Overvoltage protection makes use of a normally closed contact. The voltage needs to stay below the preset pick-up voltage for the load to be energized while the relay itself remains de-energized. If the voltage goes above the pick-up, the reverse happens, until voltage goes below the preset drop-out.

Undervoltage
Undervoltage monitoring requires a normally open contact. The load stays on and the relay is energized if the voltage stays above the preset pick-up. Voltage going below the preset drop-out de-energizes both the load and the relay.

Macromatic VAKP Series Relay Installation Instructions

Macromatic VAKP048D 48V 8 Pin Voltage Monitor Relay

Additional Product Information

Related Products
Macromatic 8 Pin Octal Socket Macromatic Hold Down Spring
Price: $5.69

Add
Price: $5.09

Add
Macromatic 70169-D 8 Pin Octal Socket Macromatic Hold Down Spring



Seifert 24V 510 BTU Peltier Control Cabinet Thermoelectric Cooler, Recessed $1,709.20
Lumberg Automation 0980 ESL 813 8 Input/8 Output, Ethernet Active M12 Distribution Block $755.91