The Macromatic PAP240 is a three phase monitor relay. This 8 pin plug in relay has a nominal voltage of 240V. It monitors against phase reversal, phase loss and undervoltage with an output of 10A SPDT. The diagram on top of the relay depicts how the LED will indicate the current status. When everything is functioning correctly, the LED is green. When an error is detected, the LED glows or blinks red. The PAP240 uses an 8 pin 70169-D octal socket. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Three Phase
  • Nominal Voltage- 240V AC
  • Minimum Voltage- 156 V
  • Maximum Voltage- 550 V
  • Power Consumption- < 40VA
  • Output- 10A SPDT
  • Phase Reversal- Trips if rotation is something other than A-B-C
  • Phase Loss- Trips if Phase A, B or C is lost
  • Undervoltage- Adjustable from 180-230V, Trips when the average of all 3 lines is less than the set point for longer than the trip delay
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10A @ 277V AC / 7A @ 30V DC, 1 HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Response Time- Restart: 1 sec, Phase Loss/Reversal: 100ms, Undervoltage: 4 sec
  • Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
  • Approvals- UL and CUL Recognized, CE, C-UL-US Listed (with Socket)

Like the rest of the PAP series, the PAP240 utilizes "True RMS voltage measurement". The analog to digital sensing circuitry in True RMS voltage measurement is able to give more precise monitoring of phases and voltages. One of the benefits of the PAP240 is its ability to still monitor all the voltages while indicating the fault, even if a phase is lost. The unit stays energized as long as the phases are detected in the right order and do not go below the undervoltage setting. Undervoltage is adjustable to a point between 75-95% of the nominal voltage. When a phase error is detected, the relay will de-energize. Until the error is fixed, the unit will remain in that state.

Macromatic PAP Series Relay Installation Manual

Macromatic Three Phase Monitor Relay Comparison Chart

240V Phase Monitor Relay

Additional Product Information

Related Products
Macromatic 8 Pin Octal Socket Macromatic Hold Down Spring
Price: $5.69

Add
Price: $5.09

Add
Macromatic 70169-D 8 Pin Octal Socket Macromatic Hold Down Spring