The Red Lion PAX2A000 PAX2 series panel meter is a universal analog input panel meter. It features a 2 line, 6/9 digit, Red/Green/Orange LCD display with 1/8 DIN housing. Features built in Modbus communications. The range of functions allows it to cover the needs of different applications. AC/DC powered. It's ideal for industrial or factory automation, process control applications, or other uses that need dual visual parameters. It is able to accommodate DC Current, DC Voltage, Process Signals, Resistance, Thermocouples or RTDs. The universal power input can accept 50 to 250 VAC or 21.6 to 250 VDC.
Features
- Universal Input - DC Current, DC Voltage, Process Signals, Resistance, Thermocouples or RTDs
- Universal Power Supply - 50 to 250 VAC or 21.6 to 250 VDC
- Dual Line, 6/9 Digit Red/Green/Orange LCD Display
- Variable Contrast & Intensity
- Meter Update Rate Up to 160/Second
- Built-In Modbus Communications
- Communications - R232, RS-485, DeviceNet and Profibus (W/Option Card)
- Setpoint & Analog Outputs (w/Option Card)
- Setpoints - Dual & Quad Relay; Quad Sinking & Sourcing
- Built-In USB Port
- NEMA 4X/IP65 - Front Panel
Red Lion PAX2A User Manual
Red Lion PAX2A Installation Instructions
Specifications
Display Positive Image LCD Top Line: Six 0.71" digits (Red/Green/Orange), Display Range - 199,999 to 999,999 Lower Line: Nine 0.35" digits (Green), Display Range - 199,999,999 to 999,999,999 Annunciators (Red): 1, 2, 3, & 4 Unit Label: 3 digits programmable (Red/Green/Orange) Power Requirements AC Power: 50 to 250 VAC, 50/60 Hz, 20 VA DC Power: 21.6 to 250 VDC, 8 W Memory Nonvolatile E2PROM memory retains programmable parameters & display values Input Capabilities Current Input: +/- 250 uADC, +/- 2.5 mADC, +/- 25 mADC, +/- 250 mADC, and +/- 2 DC Voltage Input: +/- 250 mVDC, +/- 2.0 VDC, +/- 10 VDC, +/- 25 VDC, +/- 100 ADC, and +/- 200 VDC Thermocouple Input: T, E, J, K, R, S, B, N, and C RTD Input: 100Ohm Pt (Alpha 0.00385 and 0.00392 120Ohm Nickel (Alpha 0.00672) and 10Ohm Copper (Alpha 0.00427) Resistance Input: 100Ohm, 1,000Ohm, and 10 KOhm Totalizer Time Base: second, minute, hour or day Batch: Can accumulate (gate) input display from a user input Time Accuracy: 0.01% typical Decimal Point: 0 to 0.0000 Scale Factor: 0.001 to 65.000 Low Signal Cut-out: -19,999 to 99,999 Total: 9 digits, display alternates between high order and low order readouts Excitation Power Jumper selectable Transmitter Power: +18VDC @ 50mA Reference Voltage: +2VDC, +/- 2% Reference Current: 1 mADC, +/- 2% Custom Linearization Data Point Pairs: Selectable from 2 to 16 Display Range: -19,999 to 99,999 Decimal Point: 0 to 0.0000 Ice Point Compensation: user value (0.00 to 650.00 uV/C) Standards Compliance CE Approved EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A IEC/EN 61010-1 RoHS Compliant UL Listed: File #E179259 Type 4X Indoor Enclosure rating (Face only) IP65 Enclosure rating (Face only) IP20 Enclosure rating (Rear of unit) Physical Operating Temperature: 0 C to 50 C (32 F to 122 F), 0 C to 45 C with plug in cards installed Storage Temperature: -40 C to 60 C (-40 F to 140 F) Humidity: 85% max. relative humidity (non-condensing) Altitude: Up to 2000 meters Construction: NEMA 4X/IP65 indoor use, IP20 Touch Safe, Installation Category II, Pollution Degree 2, One piece bezel/case; flame resistant; Synthetic rubber keypad; panel gasket & mounting clip Connection: High Compression Cage-Clamp Terminal Block Dimensions: 1.95" x 3.8" x 4.24"
The LCD display has a 6 digit, 0.7" top line that can be set to display in red, green, or orange. Colors on the display can be set to change with certain setpoints, to provide a quick indication of the current status. The lower line has a 9 digit, 0.35" display that shows a green readout. Either line is able to show the input, total, minimum, maximum, or set points. The LCD display also has a 3 digit indicator that can be set to show a specific unit. There are 4 keys on the front panel, with 2 of them being programmable function keys. The 24 bit resolution A/D converter has a programmable rate of 5 to 160 readings/second.
|
|
|
|
|
|
|