The Lumberg Automation 935001001 0960 IOL 385-001 Lion-P is an 8 port 5 pin M12 distribution block IO-Link Hub, with 10 digital input & 6 digital output channels. Also has 5 pin M12 A-coded IO-Link class B connection. LED indicators show port status.
Features
- Process up to 132 I/O signals as part of an IO-Link Hub/Master system
- Can send signals up to 20 M away from IO-Link Master
- Made to stand up to demanding conditions (IP 65, IP 67, IP 69K)
- Useful for upgrading from a passive to an active system, machine building, & packaging
- Reverse polarity protection
Lumberg Automation 0960 IOL 385-001 User Manual
Specifications
- Dimensions- 159mm Length x 60mm Width x 31mm Height (6.25" x 2.36" x 1.22")
- Device Type- I/O Hub
- Protocol- IO-Link
- I/O Function- 10 Digital Input/6 Digital Output
- Bus Connection- 5 Pin A-coded M12
- I/O Connection- 5 Pin A-Coded M12
- Housing Material- Nickel Plated Die Cast Zinc
- IP Rating- IP 65, IP 67, IP 69K
- Potted- Yes
- Operating Temperature- -20 C to 70 C (-4 F to 158 F)
- Storage Temperature--25 C to 85 C (-13 F to 185 F)
- Humidity- 5 - 95%
- Mean Time to Failure- 1871 years
- Contact Base Material- Gold Plated Copper Alloy
- Contact Bearer Material- Polyamide
- O-Ring- FKM
- Approvals- CE, RoHS, cULus
IO Links
- Number of Connections- 1
- Specification- V1.1.2
- IO-Link Class- Class B
- Transmission Rate / COM Mode- COM 3 (230.4 kbps)
- Cycle Time / Update Rate- Min 1 ms
- Parameter Storage- Supported
- Frame Type- Type 2 V
- Process Data Length- 4 Bytes Input Data, 4 Bytes Output Data
- Configuration- IODD, Process Data
Digital Input Channels
- Number of Channels- 10
- Number of Ports- 5
- Channel Type- Type 3 according to IEC 61131-2
- Input Wiring-2, 3, 4 wire
- Nominal Voltage- 24V DC
- Nominal Current- 5 mA
- Sensor Current Supply- Max. 700 mA per port
- Sensor Type- PNP
- Input Voltage Range- -3V DC to 5 V DC (0 signal), 11V DC to 30V DC (1 signal)
- Input Filter Time-0 to 3 ms, Configurable
- Protective Circuit- Electronically: Overload Protection, Short-circuit Protection
Digital Output Channels
- Number of Channels- 6
- Number of Ports- 3
- Channel Type- P-Switching
- Output Wiring- 2, 3 wire
- Nominal Voltage-24V DC
- Output Current per Channel- Max 0.5 Amps
- Output Current per Module- Consider 2L+ limitation of connected IO-Link Master
- Protective Circuit- Electronically: Overload protection, short-circuit protection
- Overload Behavior- Auto off and on switching / Manual restart
Electrical Isolation
- US (System Supply Voltage) / FE- 500V DC
- Uaux / FE- 500V DC
- Bus Connection / FE: 500V DC
EMC Conformance
- EMC Directive-2014/30/EU
- EN 61000-4-2 Electrostatic Discharge (ESD)- Criterion B; 4 kV contact discharge, 8 kV air discharge
- EN 61000-4-3 Electromagnetic Field- Criterion A; Field intensity: 10 V/m
- EN 61000-4-4 Fast Transients (Burst)- Criterion B, 2 kV
- EN 61000-4-5 Surge Voltage- Criterion B; DC supply lines: +/-0.5 kV / +/-0.5 kV (symmetrical/asymmetrical); For I/O ports with cables less than or equal to 30m
- EN 61000-4-6 Conducted immunity- Criterion A; Test voltage 10 V
- EN 55022 Radio Interference Properties- Class A
When connected to an IO-Link Master, it gathers up to 16 digital signals and sends them to the controller, which is ideal for applications involving a number of sensors & actuators in a tight space. It only needs one bus address (via the IO-Link Master) to group signals together, so less addresses are needed inside the network.
|
|
|
|
|
|
|
|
|
|
|
|
|